Texas HVAC Class A airflow practice
Calculate duct airflow from clear area and average velocity, interpret capture-hood reports, and study the Environmental Air Class A outline.
Where air distribution fits
Air distribution accounts for 18 of the 120 scored items in the PSI Environmental Air Class A outline. The domain includes airflow, sizing, filtration, installation, grilles and static pressure. This set practices airflow reasoning and interpreting measurements. Keep the other listed topics in your study plan.
A rectangular duct measured in inches
A clear opening is 15 inches by 12 inches. Its area is 180 square inches, or 1.25 square feet. If average velocity is 400 feet per minute, airflow is 1.25 × 400 = 500 cubic feet per minute. Divide by 144 when converting square inches to square feet.
Calculate airflow and velocityWhy a single velocity reading can mislead
Suppose four equal-area samples measure 350, 400, 450 and 400 feet per minute. Their mean is 400. Using only 450 would overstate the flow for that cross section. A representative average and the clear opening belong in the same calculation.
Practice interpreting airflow reportsRead a hood report
A passive hood relies on the air already flowing through a terminal. A powered hood has a fan that compensates for the pressure change caused by measurement. An uneven grille or a gap around the hood can let air bypass the measuring section, so the reported volume may differ from the terminal flow.