Back to Texas Environmental Air Class A practice

Texas HVAC Class A airflow practice

Calculate duct airflow from clear area and average velocity, interpret capture-hood reports, and study the Environmental Air Class A outline.

Where air distribution fits

Air distribution accounts for 18 of the 120 scored items in the PSI Environmental Air Class A outline. The domain includes airflow, sizing, filtration, installation, grilles and static pressure. This set practices airflow reasoning and interpreting measurements. Keep the other listed topics in your study plan.

A rectangular duct measured in inches

A clear opening is 15 inches by 12 inches. Its area is 180 square inches, or 1.25 square feet. If average velocity is 400 feet per minute, airflow is 1.25 × 400 = 500 cubic feet per minute. Divide by 144 when converting square inches to square feet.

Calculate airflow and velocity

Why a single velocity reading can mislead

Suppose four equal-area samples measure 350, 400, 450 and 400 feet per minute. Their mean is 400. Using only 450 would overstate the flow for that cross section. A representative average and the clear opening belong in the same calculation.

Practice interpreting airflow reports

Read a hood report

A passive hood relies on the air already flowing through a terminal. A powered hood has a fan that compensates for the pressure change caused by measurement. An uneven grille or a gap around the hood can let air bypass the measuring section, so the reported volume may differ from the terminal flow.

Compare measurement methods

Practice all six air distribution subjects in an 18-question test

Open the Class A exam simulator

Sources